Uniform Building Code: State of California ... amendments, Volume 1California Building Standards Commission, 1989 - Building laws |
From inside the book
Results 1-3 of 9
Page 1
... ramps and 18 inches past the strike edge for interior ramps . 5. Landing ... curb at least 2 inches high , or a wheel guide rail 2 to 4 inches high on ... ramps at multifamily build- ings shall be no greater than 1/4 inch per foot ...
... ramps and 18 inches past the strike edge for interior ramps . 5. Landing ... curb at least 2 inches high , or a wheel guide rail 2 to 4 inches high on ... ramps at multifamily build- ings shall be no greater than 1/4 inch per foot ...
Page 814-10
... Curb Ramps Sec . 7103. ( a ) General . Curb ramps shall be constructed at each corner of street intersections and where a pedestrian way crosses a curb . The preferred and recommended location for curb ramps is in the center of the ...
... Curb Ramps Sec . 7103. ( a ) General . Curb ramps shall be constructed at each corner of street intersections and where a pedestrian way crosses a curb . The preferred and recommended location for curb ramps is in the center of the ...
Page 814-11
... Curb Ramps . Curb ramps shall be a minimum of 4 feet in width and shall lie , generally , in a single - sloped plane , with a minimum of surface warping and cross slope . ( c ) Slope of Curb Ramps . The slope of curb ramps shall not ...
... Curb Ramps . Curb ramps shall be a minimum of 4 feet in width and shall lie , generally , in a single - sloped plane , with a minimum of surface warping and cross slope . ( c ) Slope of Curb Ramps . The slope of curb ramps shall not ...
Contents
1 | 30-2 |
Part IIIRequirements Based on Occupancy CHAPTER 5 Classification of All Buildings by Use or Occupancy and General Requirements for All Occu... | 42-4 |
Mixed Occupancy | 42-5 |
Copyright | |
51 other sections not shown
Common terms and phrases
accessible accordance addition apply approved building official building or structure CACAC California ceiling cell Code Sections comply concrete conform corridors Curb ramps dead load detectors devices dimension Division 1 Occupancies doors dwelling units elevator enclosures equipment exceed EXCEPTION existing buildings exit exterior walls fire alarm system fire-resistive construction floor area footcandles grab bar Group H grout handwashing fixture hazard height horizontal inmates installed lateral forces least less live load located masonry materials Matrix Adoption Appendix maximum minimum nonbuilding structures noncombustible nursing occupancy separation occupant load one-hour fire-resistive openings patients pedestrian percent permitted persons protected regulations reinforcement resist roof Safety Code sanitary facilities section numbers seismic shear shear wall shower smoke smoke detectors specified in Chapter specified in Section square feet stairway storage space story stress Subsection surface Table tion toilet rooms Type U.B.C. Standard Uniform Building Code ventilation vertical water closet wheelchair width