Page 3-236
... Deflectors . Deflectors of sprinklers shall be parallel to ceilings , roofs , or the incline of stairs . Exception No. 1 : pitched roof , the horizontal . When sprinklers are installed in the peak of a sprinkler shall be installed with ...
... Deflectors . Deflectors of sprinklers shall be parallel to ceilings , roofs , or the incline of stairs . Exception No. 1 : pitched roof , the horizontal . When sprinklers are installed in the peak of a sprinkler shall be installed with ...
Page 3-240
... deflectors of upright sprinklers . The bottoms of baffles shall extend downward to a level at least even with the deflectors of pendent sprinklers . ( See A - 4-4.1.7.3.4 . ) Exception No. 1 : For in - rack sprinklers , see NFPA 231C ...
... deflectors of upright sprinklers . The bottoms of baffles shall extend downward to a level at least even with the deflectors of pendent sprinklers . ( See A - 4-4.1.7.3.4 . ) Exception No. 1 : For in - rack sprinklers , see NFPA 231C ...
Page 3-255
... deflectors and the top of storage . 4-4.5.2.3 Distances below Ceiling . Sprinklers shall be positioned so that deflectors are a maximum 14 in . ( 356 mm ) and a minimum 6 in . ( 152 mm ) below the ceiling . 4-4.5.3 Location of ...
... deflectors and the top of storage . 4-4.5.2.3 Distances below Ceiling . Sprinklers shall be positioned so that deflectors are a maximum 14 in . ( 356 mm ) and a minimum 6 in . ( 152 mm ) below the ceiling . 4-4.5.3 Location of ...
Contents
General Building Limitations | 3-1 |
Administrative Fire and LifeSafety and Field Inspection Provisions | 3-3 |
Chapter | 3-9 |
Copyright | |
102 other sections not shown
Other editions - View all
Common terms and phrases
accordance ANSI applied approved assembly ASTM authority having jurisdiction beams braces branch lines brick building official ceiling cement check valve classification combustible concrete masonry construction control valve curtain deck deflectors determined devices diameter dimensions distance door drain dry pipe valve duct edge equipment exceed Exception feet fire department connection fire test fire-resistance rating flange floor flow furnace grade gypsum hangers Hazard Occupancies heat horizontal hydrostatic test installed joints joist klers knot length less limited liquid limit listed load located material maximum minimum mortar nails NFPA noncombustible Obstruction opening operation percent permitted pipe system portland cement preaction pressure protection riser roof Screw SECTION side spaced specified sprinkler system sq ft standpipe system storage structural steel structural steel columns Table temperature test sample thermocouples tion tube Type U.B.C. Standard Uniform Building Code units vertical wall thickness water supply welding width wood