Page 3-261
... drain connec- tion sized as shown in Table 4-5.3.4.2 to drain that portion of the system controlled by the sectional valve . Drains shall discharge outside or to a drain connection . [ See Figure A - 4-6.4.2 ( b ) . ] Not Less Than 4'0 ...
... drain connec- tion sized as shown in Table 4-5.3.4.2 to drain that portion of the system controlled by the sectional valve . Drains shall discharge outside or to a drain connection . [ See Figure A - 4-6.4.2 ( b ) . ] Not Less Than 4'0 ...
Page 3-262
... Drain connection for system riser . Pressure Gauge Inspector's Test Plug Table 4-5.3.4.2 Riser or Main Size Size of Drain Connection Up to 2 in . 22 in . , 3 in . , 31⁄2 in . 4 in . and larger 3/4 in . or larger 1/4 in . or larger 2 in ...
... Drain connection for system riser . Pressure Gauge Inspector's Test Plug Table 4-5.3.4.2 Riser or Main Size Size of Drain Connection Up to 2 in . 22 in . , 3 in . , 31⁄2 in . 4 in . and larger 3/4 in . or larger 1/4 in . or larger 2 in ...
Page 3-263
... drain shall consist of a valve not smaller than 1 in . ( 25.4 mm ) , piped to an accessible location . 4-5.3.5.2.4 Tie - in drains are not required on wet pipe and preaction systems . 4-5.3.5.3 Auxiliary Drains for Dry Pipe Systems and ...
... drain shall consist of a valve not smaller than 1 in . ( 25.4 mm ) , piped to an accessible location . 4-5.3.5.2.4 Tie - in drains are not required on wet pipe and preaction systems . 4-5.3.5.3 Auxiliary Drains for Dry Pipe Systems and ...
Contents
General Building Limitations | 3-1 |
Administrative Fire and LifeSafety and Field Inspection Provisions | 3-3 |
Chapter | 3-9 |
Copyright | |
102 other sections not shown
Other editions - View all
Common terms and phrases
accordance ANSI applied approved assembly ASTM authority having jurisdiction beams braces branch lines brick building official ceiling cement check valve classification combustible concrete masonry construction control valve curtain deck deflectors determined devices diameter dimensions distance door drain dry pipe valve duct edge equipment exceed Exception feet fire department connection fire test fire-resistance rating flange floor flow furnace grade gypsum hangers Hazard Occupancies heat horizontal hydrostatic test installed joints joist klers knot length less limited liquid limit listed load located material maximum minimum mortar nails NFPA noncombustible Obstruction opening operation percent permitted pipe system portland cement preaction pressure protection riser roof Screw SECTION side spaced specified sprinkler system sq ft standpipe system storage structural steel structural steel columns Table temperature test sample thermocouples tion tube Type U.B.C. Standard Uniform Building Code units vertical wall thickness water supply welding width wood