Page 3-274
... fire department access , at a constantly attended building secu- rity control center , or at both locations ... connection shall be provided to transmit a signal to a remote central station . ( b ) A distinct trouble signal shall be provided ...
... fire department access , at a constantly attended building secu- rity control center , or at both locations ... connection shall be provided to transmit a signal to a remote central station . ( b ) A distinct trouble signal shall be provided ...
Page 3-275
... Fire department connection . Hose Connection 4-6.2.3.1 The fire department connection shall be on the system side of the water supply check valve . 4-6.2.3.2 For single systems , the fire department connec- tion shall be installed as ...
... Fire department connection . Hose Connection 4-6.2.3.1 The fire department connection shall be on the system side of the water supply check valve . 4-6.2.3.2 For single systems , the fire department connec- tion shall be installed as ...
Page 3-436
... connection valves shall be provided with signs indicating their purpose . 4-2.9.3 Where sprinkler system piping ... Fire Department Connections . 4-3.1 There shall be no shutoff valve between the fire department connection and the system ...
... connection valves shall be provided with signs indicating their purpose . 4-2.9.3 Where sprinkler system piping ... Fire Department Connections . 4-3.1 There shall be no shutoff valve between the fire department connection and the system ...
Contents
General Building Limitations | 3-1 |
Administrative Fire and LifeSafety and Field Inspection Provisions | 3-3 |
Chapter | 3-9 |
Copyright | |
102 other sections not shown
Other editions - View all
Common terms and phrases
accordance ANSI applied approved assembly ASTM authority having jurisdiction beams braces branch lines brick building official ceiling cement check valve classification combustible concrete masonry construction control valve curtain deck deflectors determined devices diameter dimensions distance door drain dry pipe valve duct edge equipment exceed Exception feet fire department connection fire test fire-resistance rating flange floor flow furnace grade gypsum hangers Hazard Occupancies heat horizontal hydrostatic test installed joints joist klers knot length less limited liquid limit listed load located material maximum minimum mortar nails NFPA noncombustible Obstruction opening operation percent permitted pipe system portland cement preaction pressure protection riser roof Screw SECTION side spaced specified sprinkler system sq ft standpipe system storage structural steel structural steel columns Table temperature test sample thermocouples tion tube Type U.B.C. Standard Uniform Building Code units vertical wall thickness water supply welding width wood