Uniform Building Code |
From inside the book
Results 1-3 of 75
Page 83
Foam plastics may be used without the thermal barrier described above , regardless of the type of construction , when the foam plastic is covered by a minimum of 1 - inch thickness of masonry or concrete in a wall , floor or roof system ...
Foam plastics may be used without the thermal barrier described above , regardless of the type of construction , when the foam plastic is covered by a minimum of 1 - inch thickness of masonry or concrete in a wall , floor or roof system ...
Page 733
Chapter 7 Division 1 COVERED MALL BUILDINGS General Sec . 711. ( a ) Purpose . The purpose of this division is to establish minimum standards of safety for the construction and use of covered mall buildings having not more than three ...
Chapter 7 Division 1 COVERED MALL BUILDINGS General Sec . 711. ( a ) Purpose . The purpose of this division is to establish minimum standards of safety for the construction and use of covered mall buildings having not more than three ...
Page 736
Covered mall buildings exceeding 50,000 square feet in total floor area shall be provided with a public address system accessible for use by the fire department . Covered mall buildings of 50,000 square feet or less in total floor area ...
Covered mall buildings exceeding 50,000 square feet in total floor area shall be provided with a public address system accessible for use by the fire department . Covered mall buildings of 50,000 square feet or less in total floor area ...
What people are saying - Write a review
We haven't found any reviews in the usual places.
Contents
Part Definitions and Abbreviations | 17 |
Fireresistive Substitution | 33 |
Pedestrian Walkways | 34 |
Copyright | |
119 other sections not shown
Other editions - View all
Common terms and phrases
accordance additional allowable applied approved axial bars beam bearing bending building official Chapter column combination comply compression compressive stress computed concrete conform connections considered construction continuous covered Decking determined direction distance Division edge effective elasticity elements equipment exceed EXCEPTION exit exterior walls face factor feet fiber fire fire-resistive flexural floor foot forces Formula framing grade grain greater Group height horizontal hour inches increased inspection installed joints lateral least length less limited live load located masonry materials maximum modulus nails Occupancies one-hour openings panel parallel percent permitted placed portion protected ratio reinforcement resist roof rooms Section Select Structural separation shear side slab space span specified square steel storage story strength stress Structural Stud surface Table tension thickness Type U.B.C. Standard unit values vertical walls welds wide width wood